Surtel Kablo

transmitting energy since 1964

CATEGORY DETAILS

Ayrıntılarla Surtel Kablo

NHXMH

Standards : TS 9759 HD 21.4 S2 / VDE 250-214

Application :

These halogen-free and safety cables are used as electric installation and lighting cables for permanent installations where lots of human life and material assets are to be protected in industrial constructions, schools, hospitals, shopping and cultural centers, energy plants, airports, metros.

  • Conductor : Solid or Stranded Copper Wires
  • Insulation : XLPE Compound
  • Outer Sheath : LSFOH thermoset
  • Filler : LSFOH thermoset
Nominal cross-section
External Diameter
Construction*
Net weight
Maximum conductor DC resistance at 20 °C
Current carrying capacity
core
conductor
-
RE = Single wire round conductor RM= Multi wire round conductor
-
-
in ground (20 °C)
in air (30 °C)
-
(mm²)
(mm)
-
(kg/km)
(Ohm/km)
A
A
111,56,1RE4012,1-25
212,56,5RE527,41-34
3147,1RE704,61-45
4167,6RM923,08-57
51108,6RE1341,83-78
61169,9RM1981,15-104
721,59,2RE10212,1-25
822,510RE1327,41-34
92411,3RE1834,61-45
1031,59,6RE11412,1-25
1132,510,4RE1527,41-34
123411,8RE2144,61-45
133613,3RM2953,08-57
1431015,8RM4521,83-78
1541,510,2RE13712,1-25
1642,511,1RE1847,41-34
174413,1RE2754,61-45
184614,7RM3803,08-57
1941018,4RM6061,83-78
2041620,5RM8671,15-104
2142525,1RM13470,727-137
2243527,8RE17760,524-168
2351,510,8RE15912,1-25
2452,511,9RE2177,41-34
255414,5RE3404,61-45
265615,8RM4523,08-57
2751018,4RM6791,83-78
2851622,7RM10671,15-104
2952527,2RM16260,727-137
Quantcast