Surtel Kablo

transmitting energy since 1964

CATEGORY DETAILS

Ayrıntılarla Surtel Kablo

N2XH

Standards : TS IEC 60502-1 / HD 604 S1 / VDE 0276-604

Application :

These halogen-free and safety cables are used as electric installation and lighting cables for permanent installations where lots of human life and material assets are to be protected in industrial constructions, schools, hospitals, shopping and cultural centers, energy plants, airports, metros.

  • Conductor : Solid or Stranded Copper Wires
  • Insulation : XLPE Compound
  • Outer Sheath : LSFOH thermoset
  • Filler : LSFOH thermoset
Nominal cross-section
External Diameter
Construction*
Net weight
Maximum conductor DC resistance at 20 °C
Current Load
core
conductor
-
RE = Single wire round conductor RM= Multi wire round conductor
-
-
Clipped direct -three- phase AC
At perforated cable tray or in air -three- phase AC
-
(mm²)
(mm)
-
(kg/km)
(Ohm/km)
A
A
111,57,5RE4812,122-
212,57,9RE607,4130-
3148,3RE774,6140-
4168,8RE983,0852-
511010,2RM1461,8371-
611610,9RM2021,1596-
721,512,1RE13112,12426
822,512,9RE1637,413336
92413,8RE2074,614549
102614,8RE2553,085863
1121017,4RM3971,838086
1221618,9RM5351,15107115
1331,513,1RE14612,12223
1432,513,9RE1867,413032
153414,9RE2414,614042
163616RE3133,085254
1731018,8RM4751,837175
1831620,4RM6601,1596100
1941,514,2RE17412,12223
2042,515,2RE2257,413032
214416,3RE2974,614042
224617,5RE3893,085254
2341020,7RM5971,837175
2441622,4RM8381,1596100
2551,515RE20412,12223
2652,516,1RE2657,413032
275417,3RE3544,614042
285618,6RE4673,085254
2971,515,4RE22812,12223
30121,518,5RE34512,12223
31191,520,8RE48812,12223
3272,516,6RE3097,413032
33122,520,2RE4747,413032
34192,522,8RE6947,413032