Surtel Kablo

transmitting energy since 1964

CATEGORY DETAILS

Ayrıntılarla Surtel Kablo

H07V-R

Standards : BS 6004 / IEC 60227-3 / TS 9758 HD 21.3 S3 / VDE 0281-3

Application :

Used in covered, dry places, in fixed plants, in distribution panel, on and under plaster as laid in conduit or on insulating supports.

  • Conductor : Stranded Copper Wires
  • Insulation : PVC Compound
Cable Type
Nominal cross-section
External Diameter
Conductor Type
Net weight
Maximum Conductor DC Resistance at 20 °C
Current Carrying Capacity
-
core
conductor
-
-
-
-
In Ground (20 °C)
-
-
(mm²)
(mm)
-
(kg/km)
(Ω/km)
A
1H05V-R10,752,4Class 21224,56
2H05V-R112,6Class 21518,110
3H07V-R11,53Class 22112,117,5
4H07V-R12,53,7Class 2337,4124
5H07V-R144,2Class 2484,6132
6H07V-R164,75Class 2673,0841
7H07V-R1106,15Class 21111,8357
8H07V-R1167,1Class 21661,1576
9H07V-R1258,9Class 22580,727101
10H07V-R1359,95Class 23510,524125
11H07V-R15011,7Class 24730,387151
12H07V-R17013,35Class 26700,268192
13H07V-R19515,6Class 29220,193232
14H07V-R112017,2Class 211660,153269
15H07V-R115019,1Class 214170,124300
16H07V-R118521,3Class 217710,0991341
17H07V-R124024,3Class 223390,0754400
18H07V-R130027,05Class 229300,0601458
19H07V-R140030,4Class 237570,047546
20H07V-R150033,7Class 247340,0366626
21H07V-R163037,55Class 261760,0283720
Quantcast