Surtel Kablo

transmitting energy since 1964

CATEGORY DETAILS

Ayrıntılarla Surtel Kablo

H05Z-K ; H07Z-K

Standards : BS 7211 / TS HD 22.9 / HD 22.9

Application :

Used in business centers where human population is concentrated, shopping centers, hotels, school buindings, tunnels and similar in fire hazard areas.

  • Conductor : Bunch-Stranded Fine Copper Wires
  • Insulation : LSFOH thermoset
Cable Type
Nominal cross-section
External Diameter
Conductor Type
Net weight
Maximum Conductor DC Resistance at 20 °C
Current Carrying Capacity
-
core
conductor
-
-
-
-
In Ground (20 °C)
-
-
(mm²)
(mm)
-
(kg/km)
(Ω/km)
A
1H05Z-K10,52,35Class 59393
2H05Z-K10,752,5Class 511266
3H05Z-K112,65Class 51419,510
4H07Z-K11,53,15Class 52013,322
5H07Z-K12,53,85Class 5317,9830
6H07Z-K144,4Class 5464,9540
7H07Z-K164,95Class 5653,351
8H07Z-K1106,4Class 51131,9169
9H07Z-K1167,55Class 51641,2191
10H07Z-K1259,5Class 52520,78119
11H07Z-K13510,9Class 53420,554146
12H07Z-K15012,95Class 54850,386175
13H07Z-K17014,9Class 56720,272221
14H07Z-K19516,95Class 59130,206265
15H07Z-K112018,8Class 511590,161305
16H07Z-K115020,95Class 513960,129334
17H07Z-K118523,2Class 517570,106384
18H07Z-K124026,45Class 522480,0801459
Quantcast