Bare Copper Conductor

Standards : BS EN 60228

Application :

Used generally as power conductors at overhead elektrical distribution lines or as grounding conduktors at electrical substations, electrical test equipments and further electrical systems

  • Conductor : Annealed or Hard Drawn Stranded Copper Wires
Cable Type
Nominal Cross-Section
External Diameter
Conductor Type
Net weight
Maximum Conductor DC Resistance at 20 °C
Current Carrying Capacity
-
-
-
-
-
-
In Air (30 °C)
-
(mm²)
(mm)
-
(kg/km)
(Ω/km)
A
1Bare Copper2,52,01Class 221,937,4136
2Bare Copper42,55Class 235,74,6149
3Bare Copper63,09Class 253,043,0863
4Bare Copper103,9Class 289,0461,8386
5Bare Copper164,75Class 2140,761,15115
6Bare Copper255,9Class 2221,5440,727149
7Bare Copper357,05Class 2310,080,524185
8Bare Copper508,25Class 2416,4660,387225
9Bare Copper709,9Class 2605,59440,268289
10Bare Copper9511,4Class 2837,7260,193352
11Bare Copper12013,2Class 21074,060,153410
12Bare Copper15014,4Class 21302,2340,124473
13Bare Copper18516,2Class 21630,980,0991542
14Bare Copper24018,8Class 22158,6260,0754641
15Bare Copper30020,9Class 22713,20,0601741
16Bare Copper40023,9Class 23492,6840,047865
17Bare Copper50026,6Class 24422,720,03661083
18Bare Copper63032,8Class 25808,90,02831254